Can I use System-S Heatpump with radiators piped in Microbore piping?

Modified on Wed, 31 May, 2023 at 2:49 PM

Microbore piping is not suitable for use with a heat pump due to the poor flow rates achievable in Microbore pipe. 


System-S 6kW needs a nominal 1.0m³/hr flow rate and 10kW model needs 1.3m³/hr flow rate so it is important that pipe sizing allows for this.



Require additional help? Please follow link below

https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321


Applicable to models:  

System S, System S6, System S10, LIA 0608HWCF MS , LIA 0911HWCF MS