I have H95 error on my LA-MI heat pump. What does this mean?

Modified on Wed, 22 Feb, 2023 at 10:01 AM

 

Applicable to models:  LA6MI, LA9MI, LA12MI, LA16MI

 

Issue:  Error code H95 shown on the display. No heat, compressor is stopped.  

 

What this means: H95 means there is an issue of the supply voltage to the Fridge PCB.


Action: Engineer will need to investigate by following the flow diagram below.

Heat pump must be safely isolated from mains supply before carrying out any work! Where mains voltages are being measured, this should only be carried out by suitably qualified personel. 


 

Malfunction Decision Conditions:

The supply power is detected for its requirement by the indoor/outdoor transmission.

 

Malfunction Caused:

1 Insufficient power supply.

2 Faulty outdoor unit PCB (noise filter/main). 

 

 

 

In the UK, the mains supply must be 230V nominal -6%/+10% (216-253V). If the main supply is outside of this range at the consumer unit, then this needs to be taken up with the Distribution System Operator.


Possible parts, depending on engineer diagnosis: 

• Mains Noise Filter PCB

LA6MI / LA9MI part: X-2511023

LA12MI / LA16MI part: X-2511043


• DC filter Capacitor

LA6MI / LA9MI part: X-2511022

LA12MI / LA16MI part: X-2511042

 

• Main Refrigerant PCB, aka "Outdoor PCB" (part number depends on model of heat pump)
LA6MI part: X-2511024
LA9MI part: X-2511038
LA12MI part: X-2511044
LA16MI part: X-2511057




Require additional help? Please follow link below

https://glendimplexservice.freshdesk.com/a/solutions/articles/79000136321


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article